Basic TXV Info

TXV image


TXV image info


more detailed TXV image


How do I select a TXV for a particular application?

In order to make an accurate thermostatic expansion valve (TXV) selection, it is necessary to match the flow rate (in tons) of the TXV to the tonnage rating of the evaporator coil. The following procedure is recommended:

Sensing Bulb Location

  1. Clean the suction line near the outlet of the evaporator.
  2. The entire length of the sensing bulb must be in contact with the cleaned portion of the suction line.
  3. The sensing bulb should be placed several inches downstream of the external equalizer connection.
  4. The sensing bulb should be attached at 12 o'clock on any suction line of 7/8-inch diameter or smaller. On lines larger than 7/8-inch diameter, the bulb should be placed at either 4 or 8 o’clock. The bulb should never be placed at 6 o’clock.
  5. Always insulate the sensing bulb after installation.